Corrosion Prevention in Cooling Loops
Introduction
Corrosion in liquid cooling loops is caused by chemical,
electro-chemical, or abrasive action by the heat transfer fluid on the
wetted surfaces. Chemical product layers formed by corrosion can inhibit
suitable heat transfer between the liquid and wetted metal surfaces.
The corrosive products can introduce debris into the fluid system
affecting fluid flow, clogging up filters and tight restrictions, or
even damaging pump components. In extreme conditions, leaks can form if
enough material is removed from the fluid containment. For applications
requiring high purity of the process cooling fluid, corrosion creates
contamination of fluids whose purity requirements may be in parts per
billion level. In most applications, metal corrosion can be managed,
slowed, or even stopped by using the appropriate materials and
prevention techniques.
Materials
Stainless steel, and in particular 300 series (austenitic) stainless
steel, is inert against nearly all heat transfer fluids due to the
nature of the chromium (III) oxide passivation layer covering the
surfaces of such steel. When using deionized water, stainless steel and
nickel are considered to be appropriate for wetted surfaces. Although
stainless steel is excellent for use against corrosion in most cases, it
comes with a significant disadvantage. Stainless steel has a rather low
thermal conductivity, especially when compared to other metals such as
aluminum or copper. However, high chloride concentrations can overcome
stainless steel’s resistance.
Aluminum tends to be susceptible to corrosion, or pitting, from impurities in unpurified water. Even with a glycol solution in distilled water, both ethylene glycol and propylene glycol form acidic compounds under oxidation. This becomes corrosive on wetted surfaces and forms organic acid byproducts. To prevent this, corrosion inhibitors are customarily added to the glycol, in which case, its performance as a corrosion retardant is greatly improved above plain water. Anodization of wetted aluminum surfaces is the formation of a passivated layer of aluminum (III) oxide (Al2O3). This forms a layer thicker, by orders of magnitude than the thin natural passivated layer that forms on exposed aluminum. The natural layer is not an effective barrier against corrosion, but an anodized layer can be, provided moderate pH levels are maintained and halide ion concentration remains low. Other metals can be protected using coatings such as paint or electroplating. Anti-corrosive paints and coatings are commonly used to protect metals from degradation due to moisture, humidity, salt spray, oxidation, or exposure to a variety of environmental conditions or industrial chemicals. These corrosion resistant paints and coatings offer additional protection for metal surfaces. Metallic coatings, or plating, can also be applied to inhibit corrosion.
Copper and copper nickel alloys have good resistance against corrosion and natural resistance to biological growth. As with aluminum, however, corrosion inhibitors should be employed to avoid acidic corrosion.
Pit Corrosion
Pitting is also of particular concern in cooling loops. In a low
velocity area, a pit can form due to the localized high concentration of
a corrosion agent, such as halide ions. Once formed, the rate of
corrosion in the pit accelerates due to the volume within the pit not
exchanging fluid with the rest of the fluid volume, resulting in ever-increasing concentrations of corrosive ions and the expansion of the
pit.
Damage from this type of corrosion is particularly dangerous as it
occurs with little observable effect on appearance or performance, with
the corrosion affecting only a small portion of a surface. The
corrosion, however, propagates deeply into the metal and can create
leaks with no warnings.
As with other corrosion forms, high halide concentration, especially in the presence of oxygen and higher or lower pH levels, will create ideal conditions for pitting to occur in aluminum or steel. Stagnant flow locations should be avoided, and corrosion inhibitors for the removal of oxygen can be added.
Galvanic Corrosion
Galvanic corrosion is the result of the difference in the electrode
potential of two different materials in contact through an electrically
conductive path and a sufficiently conducting electrolyte. Specifically,
it is the natural result of materials chemically changing to their most
stable state in a system with other components able to transport or
absorb electrons and ions. The electrically conductive path will
typically occur through metallic plumbing and hardware making up the
cooling system. The less noble of the two metals will corrode over time,
dissolving into the water. Aluminum and copper, two commonly used heat
transfer metals, are examples of dissimilar metals that tend to lead to
galvanic corrosion problems in heat transfer. Steel and copper alloy
combinations can be problematic if copper is allowed to dissolve into
the fluid and plate onto steel surfaces, resulting in aggressive
galvanic action on the steel.
The selection of wetted materials that are electrochemically similar will reduce the potential between them and slow the rate of galvanic action. Consultation of the galvanic series will show the ranking of metals and their reactivity in a fluid, typically available for seawater and fresh water. The larger the difference between the two metals in question, the greater the corrosion rate on the less noble anodic metal
Erosion
Erosion is due to abrasion from solid matter debris and high fluid velocities. Proper filtration, or better yet, the use of practices described above, will reduce the amount of debris to be dealt with. The problem of high fluid velocities requires more analysis. A localized corrosion location tends to be protected from further corrosion in a stagnant volume by the passivated corrosion products, but increasing fluid velocity will push the products away and uncover unreacted and susceptible metal underneath.
Prevention Techniques
Corrosion inhibitors specific to the metal to be protected can be
added to cooling fluids, though these can require additional maintenance
to recharge the inhibitor as it will be depleted over time. Different
fluid types, such as clean distilled water, may reduce the rate of
corrosion. A dielectric heat transfer fluid can be used to eliminate the
ionic path from the corrosive metal if the process and performance
requirements were to allow its use.
Cathodic protection is a method employed to guard against galvanic corrosion. Cathodic protection uses a more sacrificial reactive metal to act as a preferential anode. It works by converting the sacrificial anodic (active) areas on a metal's surface to cathodic (passive) areas through the application of an opposing current. Proper placement of the sacrificial anode concerning the anodes and cathodes is a complex matter. Dielectric unions may be employed to break the conductive path between dissimilar metals. Special care must be taken regarding the hardware and plumbing components, ensuring that they are not a source of dissimilar metal for corrosion.
For erosion prevention, flow restrictions and direction changes create the opportunity for localized high velocity regions, even when the overall volumetric flow rate through the system seems to correspond to a manageable fluid velocity. Sudden changes in tube or pipe diameter should be avoided, especially from higher diameters to lower ones. Directional changes should allow for the maximum possible turning radius, with the elimination of sharp projections or recesses in the flow path. Of course, higher fluid velocity is typically a desired design feature in a cooling system, with improved heat transfer performance between the fluid and heat transfer surfaces. This requires a balance to be established between heat transfer performance and long-term resistance to the effects of erosion-corrosion. Velocities beyond 1-2 m/s in any location should be avoided. In addition, acceptable fluid velocities decrease depending on the susceptibility of the wetted surface in question and the temperature and aggressiveness of the heat transfer fluid, with higher temperatures increasing the rate of chemical attack on the wetted surface.
Conclusion
No metal is impervious to corrosion in every environment. However, through understanding the key conditions that cause corrosion, steadfast monitoring, and upkeep, corrosion can be contained and even controlled. Monitoring surface conditions and implementing appropriate prevention methods are vital to protecting cooling loops against metal deterioration and corrosion.
- +1 Like
- Add to Favorites
Recommend
- Laird Thermal Systems’ Prototyping Liquid Cooling Systems
- Laird Thermal Systems Commits to Sustainable Principles with SBTi-Endorsed Emissions Goals
- Laird Thermal Systems Custom Solutions for Cooling Medical X-ray Imaging Equipment
- PowerCycling PCX Elongated Thermoelectric Coolers from Laird Thermal Systems Speed up PCR Testing
- Laird Thermal Systems‘ Testing Liquid Cooling Systems Can Be Tailored According to Customer Specifications and Applicable Industry Standards
- Laird Thermal Systems’ Complete Thermal Management Systems Optimize Liquid Chromatography Equipment Capabilities
- Laird Thermal Systems NRC400 Thermoelectric Chillers for Low-Power Lasers
- Laird Thermal Systems Introduces Eco-Friendly EFC Chiller with Natural Refrigerant R-290
This document is provided by Sekorm Platform for VIP exclusive service. The copyright is owned by Sekorm. Without authorization, any medias, websites or individual are not allowed to reprint. When authorizing the reprint, the link of www.sekorm.com must be indicated.