SITE PLANNING DATA Eaton 93PM UPS 100-400 kW UPS

2022-05-13
●Notes:
■The system must be installed in a temperature and humidity controlled indoor area free of conductive contaminants.
■Continuous ambient temperature range: 0-40 °C ; Maximum relative humidity: 95 % non-condensing.
■Minimum overhead clearance for ventilation above the UPS cabinet is 500 mm.
■Minimum 900 mm clearance in front of the UPS cabinet is required for cooling air intake and servicing space.
■Minimum 450 mm of clearance required in the back of the UPS cabinet for normal system.If using top air exhaust kit with the unit then no clearance required from the back.
■When using Top air exhaust kit add 55 kg to the total weight.