SITE PLANNING DATA Eaton 93PM UPS 100-400 kW UPS
■The system must be installed in a temperature and humidity controlled indoor area free of conductive contaminants.
■Continuous ambient temperature range: 0-40 °C ; Maximum relative humidity: 95 % non-condensing.
■Minimum overhead clearance for ventilation above the UPS cabinet is 500 mm.
■Minimum 900 mm clearance in front of the UPS cabinet is required for cooling air intake and servicing space.
■Minimum 450 mm of clearance required in the back of the UPS cabinet for normal system.If using top air exhaust kit with the unit then no clearance required from the back.
■When using Top air exhaust kit add 55 kg to the total weight.
|
|
Outline Dimension Drawing |
|
|
|
Please see the document for details |
|
|
|
|
|
|
|
English Chinese Chinese and English Japanese |
|
18.05.2018 |
|
REVISION: 04 |
|
P-110000547 |
|
3.1 MB |
- +1 Like
- Add to Favorites
Recommend
- IS6630A/C/D with Three-way Output Enables DDR Power Supply Integration, Saving the Space on the PCB Board And the Required Devices
- [产品]日清纺300mA的稳压器R1526,输出电压范围为1.8~9.0V,具有过电流保护
- Citroën Ami : a 100% Electric Vehicle for New Mobility a 48V Electric Unit Which Allows the Electric Motor to Be Powered
- GSA Expands Contract with Eaton to Include Electric Vehicle Supply Equipment, Help Accelerate Low-carbon Federal Infrastructure Projects
- Eaton and Charge Enterprises Target U.S. Fleets to Accelerate Infrastructure for Electric Vehicle Charging
- UNIMOTION Mini Electric Cylinder MCE and Mini Electric Slider MSCE
- ROHM‘s 4th Generation SiC MOSFETs to be Used in Hitachi Astemo‘s Inverters for Electric Vehicles, Contributing to Longer Cruising Range and Smaller Systems in Electric Vehicles
- Electric Vehicle Malfunctions Due to Lack of Fuses or Diodes
All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.