PGR-3100 MANUAL GROUND-FAULT INDICATION SYSTEM

2018-10-25

FEATURES:
•Green LED’s indicate presence of voltage to ground for each phase of a power system.
■ A ground fault (or phase loss) is indicated when a set of LED’s is off.
■ LED’s are on when phase-to-ground voltage exceeds 30 Vac.
■ Redundant LED’s are used for reliability.
• Pressing LAMP TEST causes all LED’s to light.
• Direct connection for voltages up to 600 Vac line to line.
■ Potential transformers (PT’s) are required for voltages greater than 600 Vac.
• Provides faulted-phase indication for resistance-grounded systems and ungrounded systems.
The PGR-3100 is a self-powered ground-fault indication system. Presence of phase-to-ground voltage is indicated by redundant LED’s (two per phase). The respective phase LED’s are off when phase-to-ground voltage is less than 30 Vac. The PGR-3100 meets the National Electrical Code requirements for ground detectors for ungrounded alternating-current systems as defined in NEC 250.21. It also meets the Canadian Electrical Code requirements for ungrounded alternating-current systems in accordance with CEC 10-106(2).

Littelfuse

PGR-3100

More

Part#

Ground-Fault Indication System

More

More

User's Guide

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

June 08, 2018

Revision 6-A-060818

P95-EPI0-00000

1.1 MB

- The full preview is over. If you want to read the whole 9 page document,please Sign in/Register -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.

Contact Us

Email: