TCS SERIES
detection. It includes a solid-state output to sink or source
current when connected directly to a standard PLC digital input
module. Its normally open or normally closed output can also be
used to control relays, lamps, valves, and small heaters rated up
to 1A steady, 10A inrush. The TCS is self-powered (no external
power required to operate the unit) and available with an
adjustable actuation range of 2 - 20A or factory fixed actuation
points from 2 - 45A.
Operation
Normally Open: When a current equal to or greater than the
actuate current is passed through the toroidal sensor, the output
closes. When the current is reduced to 95% of the actuate
current or less, the output opens.
Normally Closed: When the current through the toroid is equal
to or greater than the actuate current, the output opens. When
the current is reduced below 95% of the actuate current, the
output closes. To increase sensitivity, multiple turns may be
made through the TCS’s toroidal sensor. The trip point range is
divided by the number of turns through the toroidal sensor to
create a new range. When using an external CT, select a 2VA,
0-20A output CT rated for the current to be monitored. Select
TCS adjustment range 0. Pass one secondary wire lead through
the TCS’ toroid and connect the secondary leads together.
TCS 、 P1023-20 、 C103PM 、 P1015-18 、 P1015-64 、 P1023-6 、 TCSG2A 、 TCSH2B 、 TCSGAA 、 TCSH5B 、 TCSGAB 、 TCSHAA 、 TCSH2A 、 TCSHAB |
|
DIN Rail Adapter 、 DIN Rail 、 Quick Connect to Screw Adapter 、 Female Quick Connect 、 Mounting bracket 、 Protection Relays 、 Current Sensor |
|
[ TCS ] |
|
Datasheet |
|
CE 、 CSA 、 UR |
|
Please see the document for details |
|
|
|
|
|
|
|
English Chinese Chinese and English Japanese |
|
2016/11/24 |
|
Rev: 1-A-062116 |
|
|
|
571 KB |
- +1 Like
- Add to Favorites
Recommend
All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.