FB SERIES
incandescent beacon and one beacon flasher (or auxiliary
module). The flasher and lamps are monitored by sensing the
flow of current in the circuit. If the lamp(s) or the flasher fail to
operate properly, a solid-state output and an isolated SPDT relay
energize. When connected to a site monitoring system, this
unit provides the remote beacon monitoring protection required
by the FAA/FCC. On a multiple beacon structure, one unit is
required for each two-lamp incandescent beacon (one unit per
beacon for LED beacons).
Operation
If one lamp in an incandescent beacon fails, the relay and solidstate
lamp failure outputs energize after 10s. If the flasher fails
in the ON or OFF condition, the relay and the solid-state flasher
failure output energizes after 6s. If both failures occur, all three
outputs energize after their trip delays.
Note: If both incandescent lamps fail, all three outputs will
energize. The relay and solid-state flasher failure output
energizes after 6s, and the solid-state lamp failure output
energizes after 10s.