- We offer an ARC-resistant design without an arc plenum. However, the floor-to-ceiling height must be a 10 feet (3.05 meters) minimum. Additionally, no obstructions can be located between the arc-resistant switchgear and the 10 feet (3.05 meters) ceiling (i.e., cable tray, bus duct, and so on). Lastly, the 10 feet (3.05 meters) minimum floor-to-ceiling height does not account for any housekeeping pads on which the switchgear may be placed.