D5048S SIL 3 Digital Output Driver, NE Loads, Loop Powered, DIN-Rail and Termination Board INSTRUCTION MANUAL

2022-11-09
●General Description:
■The single channel Loop Powered Digital Output Isolator, D5048S, is suitable for driving solenoid valves, visual or audible alarms to alert a plant operator, or other process control devices in Hazardous Area from a driving signal in Safe Area. It can also be used as a controllable supply to power measuring or process control equipment.
■Its use is allowed in applications requiring up to SIL 3 level (according to IEC 61508:2010 Ed. 2) in safety related systems for high risk industries.
■The Safety PLC or DCS driving signal powers the field device through the D5048S, which provides isolation and is capable of monitoring the conditions of the line.
■Short and open circuit diagnostic monitoring, dip-switch selectable and active when input power is present, provides LED indication and NC transistor output signaling.
■When fault is detected output is de-energized until normal condition is restored. Line short and open output circuit fault detection is also reflected on the PLC / DCS input circuit providing less than 10 mA consumption. In alternative, input impedance can be set to a value always lower than 2 kΩ.
■An override input, dip-switch selectable, is provided to permit a safety system to override the control signal. When enabled, a low input voltage always de-energizes the field device regardless of the input signal.
■Three basic output circuits are selectable, with different safety parameters, to interface the majority of devices on the market.
■The selection among the three output characteristics is obtained by connecting the field device to a different terminal block.
■Mounting on standard DIN-Rail, with or without Power Bus to provide fault signal, or on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2 or Class I, Zone 2.

GM INTERNATIONAL

D5048SD5048

More

Part#

SIL 3 Digital Output Driversingle channel Loop Powered Digital Output Isolator

More

driving solenoid valves ]visual ]audible alarms ]

More

User's Guide

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

2022/4/5

ISM0119-11

809 KB

- The full preview is over. If you want to read the whole 8 page document,please Sign in/Register -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.

Contact Us

Email: