BExS110D;BExS120D;BExDS110D AND BExDS120D LINE MONITORING EOL AND DIODE SCHEMATIC DIAGRAM

2022-09-14
■ Line Monitoring
● On BExS110D ; BExS120D ; BExDS110D ; BExDS120D DC units, DC reverse line monitoring can be used as required.
● All DC sounders have a blocking diode fitted in their supply input lines. An end of line monitoring diode or an end of line monitoring resistor can be connected across the +ve and -ve terminals.
● If an end of line resistor is used it must have a minimum resistance value of 3k30 and a minimum power rating of 0.5 watts or a minimum resistance value of 500Ω and a minimum power rating of 2 watts.
● The resistor must be connected directly across the +ve and -ve terminals as shown in the following drawing. The resistor leads should be kept as short as possible.

e2s

BExS110DBExS120DBExDS110DBExDS120D