B280/B480 Line Surge Protection Installation Instructions
●Basic rules :
■The way line/equipment has to be respected (see diagram)
■Imperative connection to earth.
■The selection of the protection model has to be adapted to the type of protected line .
●Earth connection :
■The length of the eath network connection conductro must be as short as possible : inf. to 0,5 m .
■Minimum section of the earth connection cable : 4 mm².
■The protection must be connected to the same earth than the protected equipment.
■The equipotentiality, between the protection and the protected equipment, must be done by the shortest way (see diagram).
●Location :
■The protection box, in general, installed at the entrance of the installation (connection box to external network), but regarding these following points :
▲Respect of the "Equipotentiality" rule.
▲Overvoltage trouble can happen inside the installation (coupling with the AC network..)
■In these case, an installation near the protected equipment is recommended.
●Maintenance:
■The B280/B480 box is maintenance free.
■Following action on a transient overvoltage, the product goes into his initial state.
●Otherwise, 2 cases of devinitive destruction can happen :
■Transient energy greater than the protection specifications (i.e. : following a "lightning" impact very close).
■Breakdown on a long duration overvoltage (i.e. : direct contact between the transmission line and AC voltage Line).
■In these two cases, the protection will go into short circuit to earth, warming the user of the trouble : this one will have to replace the protection.
B280 、 B480 、 B280-T 、 B380-T 、 B480-T 、 B280-48 、 B380-48 、 B480-48 、 B280-48D3 、 B480-48D3 、 B280-24D3 、 B480-24D3 、 B280-12D3 、 B380-12D3 、 B480-12D3 、 B280-06D3 、 B480-06D3 、 B280-06DBC 、 B480-06DBC |
|
|
|
User's Guide |
|
|
|
Please see the document for details |
|
|
|
|
|
|
|
English Chinese Chinese and English Japanese |
|
2008/5/29 |
|
|
|
N98071A |
|
78 KB |
- +1 Like
- Add to Favorites
Recommend
- Amphenol-GIS Busbars for SPD Type 2 to Meet a Fast and Pre-assembled Wiring
- ept One27® SMT PCB Connectors with a Pitch of 1.27mm is Suitable for Board-to-board Applications ∣ video
- The Installation Advantages, Structural Features and Product Applications of WAGO‘s 2273 Series Compact Wire Connectors ∣ Video
- ELETE Press-fit With High Electrical Reliability, Suitable For Communications, Automotive Electronics, Medical And Other Industries
- Greenconn荣获邓白氏企业认证,实力彰显行业领先水平
- 需要充电吗?具有开尔文源引脚的SiC MOSFET DIF120SIC053-AQ加速电动汽车充电过程
- RARA Would Like to Give Customers a “One-stop Solution” with All Kinds of Resistive Products
All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.