MAVOWATT® 50 Energy and Power Disturbance Analyzer

2022-02-24
●Features and Characteristics
■Eight Mutually Isolated Measurement Inputs
▲The MAVOWATT 50 is equipped with | eight isolated measuring circuits (4 each for voltage and current) for simultaneous measurement of phase and neutral conductor voltage and current. By connecting a suitable measuring transducer, the fourth channel can be used alternatively for acquiring other physical quantities, e g. the temperature of a motor or transformer, or wind speed at a wind power turbine. Mutual isolation of the measuring channels provides for enhanced operating safety and prevents circulating currents, or allows for simultaneous measurement in two separate electrical circuits, e g. at the input and the output of a rectifier.
◆Four analog voltage measurement inputs, namely Uli, Uu, Ul3 and Ul4, for direct or alternating voltages of up to 900 V @ measuring category III or 600V@CAT IV. Measurements in medium-voltage systems can be performed by means of voltage transformers at the system side Their transformation ratios can be set individually for each input.
◆Four analog current measurement inputs, namely In, Il2, lu and Il4, laid out as voltage inputs (see Technical Data for measuring ranges) for connecting shunts or (clip-on) current transformers with voltage output. If flexible current sensors are utilized (Rogowski coils), a 9 V voltage output can be used to supply them with power. The transformation ratio can be set individually for each input.
■Eight Digital Status and Control Inputs
▲Four binary status inputs, namely a, b, c and d. for displaying and recording ON/OFF statuses, for example the operating states of machines, equipment and alarm devices. The inputs are equipped with a common floating reference point, and are S〇 compatible (max. 30 V).
▲Four binary control inputs, namely e, f, g and h. for controlling device functions, for example starting / stopping recordings. These are also floating inputs, and are TTL compatible.

Gossen Metrawatt

Z207GZ207FZ821BZ225AZ208BZ231BZ201AZ202AZ203AZ860AZ861AZ862AZ863AM816AZ753AZ3512AWZ11BZ13BMETRA-FLEX 3003METRA-FLEX 3001MAVOWATT 50

More

Part#

Energy and Power Disturbance Analyzer

More

Energy Technology ]Building Services ]Operations Technology ]Electrical Engineering ]Drive Technology ]Vehicle Manufacturing ]Aircraft Manufacturing ]Shipbuilding ]

More

Datasheet

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

2010/7/4

3-349-342-03

383 KB

- The full preview is over. If you want to read the whole 12 page document,please Sign in/Register -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.

Contact Us

Email: