GALAXY VM 1 MODULE UPS WITH CLASSIC BAH CAB& O/P XFMR SYSTEM ONE LINE DIAGRAM

2022-02-22
●NOTES:
■1.INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL,STATE AND LOCAL CODES.
■2.REFER TO PRODUCT DOCUMENTATION FOR ADDITIONAL DETAILS PRIOR TO INSTALLATION AND SITE PREPARATION WORK.
■3.DRAWING DEPICTS POWER SYSTEM CONNECTIONS AND IS NOT REPRESENTATIVE OF PHYSICAL LAYOUT,
PLEASE REFER TO MECHANICAL DRAWINGS FOR PHYSICAL LAYOUT.
■4. INPUT AC SOURCE TO BE 480V AC 3PH, 3 WIRE SYSTEM:-3 WIRE+GROUND,
■5. AC CABLING TO BE 600V RATED, 3 WIRE+GROUND, PROVIDED BY OTHERS.
■6. BAHERY RUNTIME IS THEORETICAL AND CALCULATED BASED ON DATA PROVIDED BY BAHERY MANUFACTURER ASSUMING OPTIMUM ENVIRONMENT AND LOAD CONDITIONS.
■7. BUSBAR LINKS APPLICABLE FOR SINGLE MAINS ONLY. SHOULD BE REMOVED FOR DUAL MAINS SYSTEMS.
LUGS ARE NOT PROVIDED. SEE MECHANICAL SUBMITTAL PACKAGE AND INSTALLATION MANUAL FOR ADDITIONAL TERMINATION DETAILS.
■9.A GROUND BONDING JUMPER MUST BE CONNECTED TO THE T TERMINAL GEC IS REQUIRED FOR 3 WIRE INPUT/OUTPUT ONLY.
■10. SYSTEM OUTPUT OCPD AND CABLING SHALL BE PROVIDED BY OTHERS.CABLING SHALL COMPLY WITH LOCAL OR NATIONAL CODE TAP RULES.SEE SHEET-3 FOR DETAILS. AC CABLING TO BE NOT LESS THAN 250V RATED.
■11. BONDING JUMPER PROVIDED BY SCHNEIDER ELECTRIC.
■12. OUTPUT GROUND FAULT DETECTION IS NOT PROVIDED FOR UNDERGROUND OR HRG INSTALLATION. CONTACT Schneider Electric FOR ASSISTANCE.

SCHNEIDER

GVM160KG65TFCBC15C1-SD

More

Part#

More

More

Outline Dimension Drawing

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

2019/8/16

REV 3

371 KB

- The full preview is over. If you want to read the whole 3 page document,please Sign in/Register -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.

Contact Us

Email: