VLF CR-80 kV test system High-performance VLF test system for up to 46 and 66 kV rated cables

2021-12-28
●DESCRIPTION
■This high-performance 0.1 Hz VLF test system for cables with cosine-rectangular Stages works in accordance with VDE, IEC and IEEE standards.
■According to most standards and regulations cable circuits must be tested after installation, after repair or for maintenance purposes. The VLF CR-80 kV test system can be used to test cables with 3 U-o with operating voltage levels up to 46 kV The system consists of a control unit and an HV unit. The high test capacity of 2.5 pF allows to simultaneously test all three phases with the standardized 0.1 Hz test frequency. Positive and negative DC testing of cables and connected switchgears can be carried out by switching over to DC Mode. Aside from cable and sheath testing, the system can also be used to precisely pinpoint sheath faults (in combination with a step voltage probe like the ESG NT).
■Using 0.1 Hz cosine-rectangular voltage, weak spots in the cable can be safely brought to break-down. The benefits of the VLF method with 0.1 Hz cosine-rectangular voltage have been confirmed by extensive scientific research as well as practical field tests. The proven voltage is recommended by Cenelec 620/621, IEC 60502-2 and IEEE 400.2 standard
■The VLF CR-80 kV test system can be used as stand-alone system (permanently installed in a transportation container for operations such as cable testing on offshore wind-farms) or fully integrated into a test and fault location system. The integrated safety system and breakdown recognition software maximise safety.
■Furthermore, the leakage current measurement enables a qualitative assessment of the cable cable, and the protocol function allows test data to be stored for further reporting purposes.
●FEATURES
■Ideal for testing long 36/45 kV submarine cables
■ High test capacity
■Maximises user safety through automatic discharge of the test object and earth loop monitoring
■Breakdown recognition
■VLF, DC and sheath fault pinpointing in one device
●Test with 3 Uo for 46 kV cables or 2 Uo for 66 kV cables
●Can function as a stand alone system or be integrated into the Centrix Test Van
●Ideal for standard compliance testing of long cables such as submarine cables
●Reporting, breakdown recognition and leakage current measurement
●Integrated discharge system

Megger

VLF CR-80 kVVLF CR-80-BVLF CR-80-P

More

Part#

High-performance VLF test system

More

More

Datasheet

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

2021/08/22

V02

360 KB