Littelfuse Protection Relay Technical Note-Ground Check:GC-13 : SPLITTER-BOX DUAL-CABLE MONITORING WITH AN SE-135
●When an SE-TA24A and an SE-TA24B are used as a set, the parallel combination has the 12-V Zener characteristic required by the SE-135 as a valid ground-check-loop termination. An open or short in the ground-check loop of either cable will result in an SE-135 ground-check trip; no indication is provided of which cable is faulted.
●To be able to energize either single cable independently, a live-end cover fitted with an SE-TA24A or an SE-TA24B, as required, must be available at the splitter box.
|
|