TCS SERIES Current Sensor
● Operation:
■ Normally Open: When a current equal to or greater than the actuate current is passed through the toroidal sensor, the output closes. When the current is reduced to 95% of the actuate current or less, the output opens.
■ Normally Closed: When the current through the toroid is equal to or greater than the actuate current, the output opens. When the current is reduced below 95% of the actuate current, the output closes. To increase sensitivity, multiple turns may be made through the TCS’s toroidal sensor. The trip point range is divided by the number of turns through the toroidal sensor to create a new range. When using an external CT, select a 2VA, 0-20A output CT rated for the current to be monitored. Select TCS adjustment range 0. Pass one secondary wire lead through the TCS’ toroid and connect the secondary leads together.
TCS SERIES 、 TCS 、 TCSG2A 、 TCSGAA 、 TCSGAB 、 TCSH2A 、 TCSH2B 、 TCSH5B 、 TCSHAA 、 TCSHAB |
|
Protection Relays 、 Current Monitoring Relays 、 Current Monitoring Transducers 、 Current Sensor |
|
|
|
Datasheet |
|
|
|
Please see the document for details |
|
|
|
|
|
|
|
English Chinese Chinese and English Japanese |
|
062116 |
|
Rev: 1-A-062116 |
|
|
|
527 KB |
- +1 Like