OV-12/24 SERIES INSTALLATION INSTRUCTIONS

2021-04-06
VOLTAGE ADJUSTMENT RANGE: 6.2 – 33VDC
●ADJUSTMENT PROCEDURE:
■REFER TO CHART 1 FOR SUGGESTED OVP TRIGGER VOLTAGES.
■CONNECT TEST CIRCUIT AS SHOWN IN FIGURE A. TEST VOLTAGE SOURCE MAY BE ANY POWER SUPPLY WITH A SHORT CIRCUIT LIMIT OF LESS THAN 8 AMPS (OVP-12) OR 20 AMPS (OVP-24).
■ENERGIZE AND ADJUST THE TEST VOLTAGE SOURCE TO THE DESIRED OVP VOLTAGE.
■ROTATE THE OVP ADJUSTMENT POT CCW (FROM ITS MAXIMUM CW POSITON) UNTIL THE OVP FIRES AS INDICATED BY A BY A 1 VOLT READING ON M1. LEAVE THE POT IN THIS POSITION, UNIT IS NOW READY FOR INSTALLATION INTO POWER SUPPLY.
■BOLT THE OVP ONTO THE POWER SUPPLY USING THE MOUNTING HOLES PROVIDE. CONNECT THE WHITE (+) LEAD TO THE POSITIVE OUTPUT AND THE BLACK (-) LEAD TO THE NEGATIVE OUTPUT.

SL POWER

OV-12 SERIESOV-24 SERIESOV-12OV-24

More

Part#

More

More

User's Guide

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

5/4/06

Rev. A 5/4/06

41-35625-0001

57 KB