How many circuits can I have on the switches loadside using the multi-wire lug kits?
Published:2024-05-08
-
- 用户_5489 (0)
- The 3-port MULTI-wire lug for the 30 and 60 A switches and the 6-port multi-wire lug for the 100 A switch add a minimum of 3 and 6 circuits respectively. Additional circuits are possible as these lugs are also dual wire rated if using specific wire types and gauges. The 200 A switch has 3- and 6-port multi-wire lugs available. Thus, a minimum of 3 or 6 additional circuits are possible for the 200 A switch. These are dual wire rated depending on the specific wire types and gauges involved. As with all the multi-wire lugs, the amp rating for the additional circuits must be within the permitted conductor sizes. See data sheet 10801 for specific combinations.