Can I use the fork terminals on the CCP2 (up to 100 A) for my lineside and loadside connection, or do I need to use the box lug connection?
Published:2024-04-10
-
- 用户_5489 (0)
- The 100 A and below ccp2 switches include lineside and loadside box lug and fork terminal connections. The fork terminal is used to connect the PLC fuse monitor accessory, if required. If the PLC fuse monitor is not installed, the fork terminals can be used as the lineside and loadside connection since they’re rated for 30 A max. Both box lug and the fork terminal connections can be used at the same time, providing increased application flexibility.