SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

2022-06-10

The SE-125 is a combination ground-fault and high-output, ground-check monitor for non-hazardous,resistance-grounded installations. The high-output, ground-check circuit is suitable for slip-ring or commutated-load applications. Two Form C output contacts are provided for contactor control, or for shunt or undervoltage operation ina breaker trip circuit. Two Form C contacts are provided for remote indication.
Ground-fault current is sensed by a CT200 series window-type current transformer with a 5-A secondary. A trip level of 0.5 A, 2.0 A, or 4.0 A is switch selectable for use with a 5-A, 15-A, or 25-A grounding resistor. This corresponds to 0.25%, 1.0%, or 2.0% of the primary rating of the current transformer. Trip time is adjustable from 0.1 to 2.0 seconds.
The SE-125 ground-check circuit recognizes the SE-TA12A’s 12-volt Zener characteristic as a valid end-of-line completion. This is the only passive characteristic that will satisfy the ground-check circuit’s multi-level drive,allow induced currents to circulate in the ground-check loop, survive a phase-to-ground-check fault, and clamp the ground-check voltage during the fault.

Littelfuse

SE-125CT200CT200L

More

Part#

CHECK MONITOR

More

More

Technical Documentation

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

FEBRUARY 14, 2001

REVISION 3

S95-C125-00000

1008 KB

- The full preview is over. If you want to read the whole 12 page document,please Sign in/Register -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.

Contact Us

Email: