Customer Integration Guidelines: Senseair Sunrise and Sunlight CO₂
▲Temperature and humidity operating range
●At higher than specified absolute humidity and relative humidity levels, statedaccuracy cannot be guaranteed
●At lower temperatures than specified, e.g. freezing temperatures, there is risk of micro-condensation and ice crystals forming inside the optical bench, causing diffractions to the irradiated IR optical path, and greatly impacting performance. If operation below dew point or in freezing environments is required, please contact Senseair
●At higher temperatures than specified, the internal temperature-compensation for gas concentrations will be less accurate. If calibrated accuracy and function is required for wider temperature ranges, please contact Senseair
▲Warm-up time
●There is NO warm-uptime required for the Senseair Sunrise and Sunlight, the very first measurement would be accurate within stated accuracy specification andaverage RMS noise after a reboot or power cycle. This due to the miniscule circuitry-heating of Senseair sensor chipset, and with the typical integration of several samples per presented concentration value and measurement period
●This is important for integration design, as the power cycle in single measurement mode can be optimizedgreatly by working perfectly by only making one measurement before it reverts back to low-power sleep or shutdown. Every measurement is trustworthy with this sensor.
[ commercial and residential buildings ][ industrial applications ] |
|
User's Guide |
|
|
|
Please see the document for details |
|
|
|
|
|
|
|
English Chinese Chinese and English Japanese |
|
2022/2/25 |
|
Rev 11 |
|
TDE7318 |
|
1.7 MB |
- +1 Like
- Add to Favorites
Recommend
All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.