Recommended types X and KS link primary fusing for distribution transformers Technical Data
■ Table shows recommended fuse ratings based on the use of Eaton Cooper Power series time current characteristics defined for Type X Link in K-41000AB, February, 1981, and Type KS Link in K-21000AB, February, 1981.
■ Recommendations provide overload protection (fusing ratio) between 200% and 300% rated load.