MLD-18 Mini AC Leakage Current Clamp Indicator INSTRUCTION MANUAL
■It can be attached to each circuit such as a distribution board to detect leakage of 15mA or more, and to display and hold the LED.
●SPECIFICATIONS
■Inside Diameter of CT:φ18mm
■Setting value: AC 15mA
■Accuracy:±5% for AC 15mA in 23°C±5°C 80% RH or less (50/60Hz)
■Limitation of Voltage Circuit: less than AC 600V (insulated conductor)
■At the time of detection:The LED will blink when detection leakage current exceeds setting value. By pressing the reset switch, the blinking of the operation lamp can be reset.
■Sampling rate: 1times/20ms
■Operating Temperature: 0~40°C, less than 80%RH (non-condensing)
■Storage Temperature: -10~60°C, less than 70%RH (non-condensing)
■Dimension & Weight: 45(W)x101(H)x23(D)mm, 70g
■Power supply: 1.5V(LR-44 or SR-44) battery×2. The red LED lights up when the operating voltage is below
■Standard Accessories: Soft case, Batteries, Instruction manual
|
|