RGK600 -RGK601 RGK600SA -RGK601SA Generating set controller
■The RGK600 and RGK601 control units have been designed to offer state-of-the-art functions for genset applications, both with and without automatic mains outage control. Built with dedicated components and extremely compact, the RGK600-RGK601 combine the modern design of the front panel with practical installation and LCD screen that provides a clear and intuitive user interface.
●Description
■4 versions available:
◆RGK600 –AMF with Pick-up speed input
◆RGK600SA –Stand alone with Pick-up speed input
◆RGK601 –AMF with CAN bus interface
◆RGK601SA –Stand alone with CAN bus interface.
■Genset control with automatic management of mains-generator switching (RGK600-RGK601) or remote starting management (RGK600SA-RGK601SA).
■128x80 pixel, backlit LCD screen with 4 grey levels.
■5 keys for function and setting.
■2 LEDs indicate operating modes and states.
■5-language text for measurements, settings and messages.
■Advanced programmable I/O functions.
■4 alternative functions can be managed, selecting the same with a selector.
■Fully user-definable alarms.
■High accuracy TRMS measurement.
■3-phase + neutral mains voltage reading input.
■3-phase + neutral genset voltage reading input.
■3-phase load currents reading input.
■12-24 VDC universal battery power supply.
■Front optical programming interface: galvanically isolated, high speed, waterproof, USB and WiFi compatible.
■3 analog inputs for resistive sensors:
◆Oil pressure
◆Coolant temperature
◆Fuel level
■5 +3 digital inputs:
◆4 programmable, negativeo3 programmable, negative, used as an alternate function of resistive inputs
◆1 for emergency-stop pushbutton, positive
■6 digital outputs:
■6 protected positive static outputs
■Power control from external start (RGK600SA –RGK601SA)
■Engine speed reading W, pick-up and AC from permanent magnet b.c. input (RGK600-RGK600SA)
■CAN bus-J1939 engine ECU control communications interface (RGK601-RGK601SA).
■Memorization of last 50 events.
■Support for remote alarms.
■IP54 front protection. Upgrade to IP65 with optional gasket
|
|
User's Guide |
|
|
|
Please see the document for details |
|
|
|
|
|
|
|
English Chinese Chinese and English Japanese |
|
10/02/2014 |
|
|
|
MHIT201A1012_FR-GB |
|
876 KB |
- +1 Like
- Add to Favorites
Recommend
All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.