SERIESONE DR AC & DC OUTPUT SINGLE CHANNEL & AC OUTPUT DUAL CHANNEL SOLID STATE RELAYS INSTALLATION GUIDE

2022-09-24
Please read all installation instructions before using SeriesOne DR SSRs.
● Install the relay on the DIN rail (as shown in drawing).
● Wire the relay to the input side. AWG #22 minimum, AWG #16 maximum (0.3-1.3 mm²). Temperature rating of 111ºC.
● Wire the relay to the output side. AWG #22 minimum (0.3 mm²), AWG #14 (2.1 mm²) x 2 or AWG #12 (3.3 mm²) x 1 (standed/solid) maximum. Temperature rating of 111ºC.
● Maximum recommended terminal screw torque input 4.4 lb-in (0.5 Nm) & output 7 lb-in (0.8 Nm).
● If multiple units are installed be sure to follow derating curves (reverse side of this sheet).