D5000 series ATEX Safety Instruction Manual
■D5000 series are apparatus installed into standard EN/IEC60715 TH 35 DIN-Rail located in Safe Area or Zone 2 within the specified operating temperature limits (for complete details please refer to table 1). They can be mounted with any orientation over the entire ambient temperature range.
■The end user is responsible to ensure that the operating temperature of the module is not exceeded in the end use application.
■Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts.
■Electrical connections are accommodated by polarized removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage. Connect only one individual conductor per each clamping point, use conductors up to 2.5 mm2 and a torque value of 0.5-0.6 Nm. The wiring cables have to be proportionate in base to the current and the length of the cable.
■D5000 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/IEC 60079-14 Explosive atmospheres - Part 14: Electrical installations design, selection and erection), following the established installation rules.
According to EN/IEC61010, D5000 power s叩plies must be connected to SELV or SELV-E s叩plies.
■All circuits connected to D5000 must comply with the overvoltage category II (or better) according to EN/IEC 60664-1.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury.
■For those models having a relay output: connect relay contacts checking the load rating to be within the contact maximum rating. To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation instructions (for complete details please refer to table 2, it present).
■For those models having a transistor output: connect transistor contacts checking the load rating to be within the contact maximum rating (for complete details please refer to table 2, if present).
■For those models having contacts rated more than 50 Vac or 75 Vdc: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential.
■Storage: if the unit is not installed directly on a system (parts for spare or expansion with long storage periods), it must be conveniently stocked. Stocking area characteristics must comply with the following parameters: temperature -45 to +80°C; humidity 0 to 95%.
■Vibration: no prolonged vibration should be perceivable in the stocking area to avoid loosening of parts or fatigue ruptures of components terminals.
■Pollution: presence of pollutant or corrosive gases or vapours must be avoided to prevent corrosion of conductors and degradation of insulating surfaces.
D5000 series 、 D5000 、 5700 、 D5011 、 D5014 、 D5015 、 D5020 、 D5030 、 D5031 、 D5032 、 D5034 、 D5036 、 D5037 、 D5038 、 D5039 、 D5040 、 D5048 、 D5049 、 D5062 、 D5072 、 D5072-087 、 D5072-096 、 D5072-099 、 D5090 、 D5090-086 、 D5091 、 D5093 、 D5094 、 D5095 、 D5096 、 D5097 、 D5098 、 D5099 、 D5202 、 D5212 、 D5231 、 D5240 、 D5244 、 D5254 、 D5263 、 D5264 、 D5273 、 D5290 、 D5290-078 、 D5291 、 D5293 、 D5294 、 D5295 、 PSD5201 、 D5011 series 、 D5014 series 、 D5015 series 、 D5020 series 、 D5030 series 、 D5031 series 、 D5032 series 、 D5034 series 、 D5036 series 、 D5037 series 、 D5038 series 、 D5039 series 、 D5040 series 、 D5048 series 、 D5049 series 、 D5062 series 、 D5072 series 、 D5072-087 series 、 D5072-096 series 、 D5072-099 series 、 D5212 series 、 D5231 series 、 D5240 series 、 D5244 series 、 D5254 series 、 D5263 series 、 D5264 series 、 D5273 series 、 PSD5201 series |
|
|
|
User's Guide |
|
|
|
Please see the document for details |
|
|
|
|
|
|
|
English Chinese Chinese and English Japanese |
|
2022/5/26 |
|
|
|
ISM0156-16 |
|
261 KB |
- +1 Like
- Add to Favorites
Recommend
All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.