CP10 Series Power supply CB TEST CERTIFICATE (FR_704914/A1)
●PULS GmbH
●Ratings and principal characteristics:
■CP10.241...
◆Input:
▲AC 100-240V (-15%/+ 10%), 3,3-1 ,4A, 50-60Hz
▲DC 110-150V (+20%), 3,0-2,2A
◆Output:
▲DC 24V, 12A (below +45°C)
▲10A (at +60°C)
▲7 5A (at +70°C)
▲Derate linearly between +45°C and +70°C
▲Ambient temperature range: -25°C to +70°C
■CP10.242...
◆Input:
▲AC 100-240V (-15%/+10%),3,3-1,4A, 50-60Hz
▲DC 110-300V (+20%),3,0-1,1A
◆Output:
▲DC 24V, 12A (below +45°C)
▲10A (at +60°C)
▲7,5A (at +70°C)
▲Derate linearly between +45°C and +70°C
▲Ambient temperature range: -25°C to +70°C
■CP10.241-70
◆Input:
▲AC 220-240V (-15%/+10%),1,6A, 50-60Hz
▲DC 220V (-23%/+63%), 1,4A
◆Output:
▲DC 29V,10A (continuous)
▲13A (for peak currents up to 1s) Max. duty cycle of 0.3 for peak currents
▲Ambient temperature range: -25°C to +50°C
●A sample of the product was tested and found to be in conformity with:
■IEC 61010-1:2010 + A1:2016
■IEC 61010-2-201:2017
CP10 Series 、 CP10 、 CP10.24x-ww 、 CP10.24x-Sz-ww 、 CP10.24x-Ry-ww 、 CP10.241-70 、 CP10.241... 、 CP10.242... |
|
|
|
Test Report |
|
|
|
Please see the document for details |
|
|
|
|
|
|
|
English Chinese Chinese and English Japanese |
|
28/08/2019 |
|
|
|
FR_704914/A1 |
|
782 KB |
- +1 Like
- Add to Favorites
Recommend
All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.