DP41-B Isolated Analog Output Option OPERATION MANUAL
■Precise analog levels are generated from digital code using a 14-bit DAC chip.
■Voltage (to 10 V) is available at the same time as current (to 22 mA), but the total current drawn should not exceed 24 mA.
■Load resistance for the voltage output can be as low as 500 ohms (20 mA at 10 V out) when current output is not used.
■Loop resistance for the current output can be as high as 600 ohms (12 volts compliance) with negligible current from the voltage output.
■Both outputs are galvanically isolated from both power and measurement circuits of the meter.
■Precision calibration is applied by the meter to either the voltage output or the current output (but not to both simultaneously). When both outputs are used simultaneously, the non-calibrated output is stable but does require external adjustment if fine-trimming is required.
■Independent, 14-bit resolution OuTput SCale and OFfset (OT.SC.OF) can convert a wide range of meter readings to the desired current or voltage output span.
■The output resolution permits good accuracy for turndown ratios (offset/span) as high as 100:1.
■50° to 104°F (10° to 40°C) accuracy within 0.1% after installation calibration.
■10% to 90% step response time is 6 milliseconds (plus filter delay, if any, programmed for the analog output).
■Configurable so that output will track the PEAK or VALLEY measurement.
|
|