SCV-20001 SPEC.CONTROL DRAWING UNISTAR V UPS

2022-05-11
●SPECIFICATIONS:SINGLE PHASE ON-LINE DOUBLE CONVERSION UNINTERRUPTIBLE POWER SUPPLY 2000VA/1800W
●INPUT
■RATED VOLTAGE: 100–120 VAC
■FREQUENCY RANGE: 50/60 Hz
■POWER FACTOR: ≥0.99 AT NORMAL VOLTAGE
●ОUTPUT
■NOMINAL VOLTAGE: 100*/110*/115*/120 VAC ±1%
■FREQUENCY SYNC RANGE: 47-53 Hz or 57-63 Hz
■FREQUENCY RANGE (BAT. MODE): 50Hz ±0.5Hz or 60Hz ±0.5Hz
■CURRENT CREST RATIO: 5:1 (MAX.)
■HARMONIC DISTORTION: ≤2% THD (UINEAR LOAD), 8% MAX. (BATTERY MODE BEFORE SHUT DOWN)
■EFFICIENCY: UINE MODE: 88% TYPICAL. 90% PEAK
BATTERY MODE: 85% TYPICAL, 88% PEAK
■DERATE CAPACITY TO 95% WHEN THE OUTPUT VOLTAGE IS ADJUSTED TO 115VAC. DERATE CAPACITY TO 90% WHEN THE OUTPUT VOLTAGE IS ADJUSTED TO 110VAC. DERATE CAPACITY TO 80% WHEN THE OUTPUT VOLTAGE IS ADJUSTED TO 100VAC.
●BATTERY
■BATTERY TYPE: 12V 9AH
■NUMBER OF BATTERIES:4
■TYPICAL RECHARGE TIME: 4 HOURS RECOVER TO 90% CAPACITY
■CHARGING CURRENT (MAX.): 1A AT 27.4 VDC ±1%. 4A OR 6A FOR EXTERNAL BATTERIES
■WEIGHT: 47 LBS (21 KG)
●ENVIRONMENTAL
■OPERATING TEMPERATURE: 0℃-40℃ (32°F-104°F)(THE BATTERY LIFE WILL DECREASE WHEN > 25℃ (77°F))
■ALTITUDE: <1000m (3281 FT), 2000m (6562 FT) MAX.
IF THE UPS IS INSTALLED OR USED IN A PLACE WHERE THE ALTITUDE IS ABOVE THAN 1000M, THE OUTPUT POWER MUST BE DERATED ONE PERCENT PER 100M.
■HUMIDITY: 20-90% RH AT 0℃ - 40℃ NON-CONDENSING
■NOISE: <50 dBA (AT 1 METER)
■UL USTED TO UL1778

Staco Energy

SCV-2000183008

More

Part#

UPS

More

More

Outline Dimension Drawing

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

11/22/17

096-4332

144 KB

- The full preview is over,the data is 1 pages -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.

Contact Us

Email: