OML SERIES OmegaLynx® Wireless Modules
●Transmitter and receiver modules are available with four (4) channels of 4-20mA or 1 to 5 Volt process loop data. The user process data transmission is unidirectional, i.e. - a transmitter/receiver pair sends all data in one direction only. Consequently, the transmitter module is the data input module,connecting to the 4-20 mA loop sensors, and the receiver module is the data output module, connecting to the process control loop instrumentation equipment input channels. The transmitter module samples each channel 10 times per second.
●The modules have seventeen (17) terminals arranged in three terminal blocks.Each data channel has three (3) connections, the power input uses three (3)terminals, and (2) connections are a set of dry contacts (normally open) that will close upon a communication link failure. The input and output channels are unipolar. The signal input range is from zero (0) volts to positive 5 volts,full scale, on the transmitter module and 4 milliamperes to 20 milliamperes on the receiver module. Each module has an RF connector for the antenna and three Light Emitting Diode (LED) indicators.
|
|