IMX12-DI01-2S-2T-0/ 24VDC Isolating switching amplifier 2-channel

2022-03-29
●Sensors according to EN 60947-5-6 (NAMUR) or potential-free contacts can be connected to the IMX12-DI01-2S-2T-/24VDC isolating switching amplifier. The device is equipped with intrinsically safe input circuits and can be installed in zone 2. A DIP switch on the device allows to toggle between 2-channel or 1-channel operating mode with signal doubling. The output circuits are equipped with two potential-free transistors with high cut-off frequency (10 kHz). The device complies with the requirements of the NE21.
●The devices feature DIP switches on the front. This allows to select between the output mode, the input circuit monitoring, as well as toggle between signal duplication and 1-channel operation. When using mechanical contacts, either line monitoring must be switched off or the contact must be wired with resistors (see wiring diagram).
●The green LED indicates operational readiness. An error in the input circuit causes the red LED to flash according to NE44. Then, the transistor of the corresponding output circuit locks.
●The device can be used in safety circuits up to SIL2 (high and low demand according to IEC 61508).
●The device is equipped with removable screw terminals.
■2 transistor outputs (ð 10kHz)
■Switchable: 2-channel or signal doubling
■Output mode adjustable (NO/NC mode)
■Input circuits monitored for wire-break/ short-circuit (ON/OFF switchable)
■Complete galvanic isolation
■Input reverse-polarity protected
■Removable screw terminals
■ATEX, IECEx, NEPSI, cUL, cFM, INMETRO, Kosha, TIIS, TR CU EAC, DNV, GL
■Installation in zone 2
■SIL 2

TURCK

IMX12-DI01-2S-2T-0/ 24VDC7580020

More

Part#

Isolating switching amplifier

More

More

Datasheet

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

2020-01-18

Edition • 2020-01-18

245 KB

- The full preview is over. If you want to read the whole 4 page document,please Sign in/Register -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.

Contact Us

Email: