STEINEL IECC 2015 Solution Design Guide
● Use of occupancy sensor provides automatic all OFF (C405.2.1.1.1).
●All sensors to be set to partial ON or manual ON to meet the code (C405.2.1.1.2).
●Momentary switch is used to provide manual control of the lighting except lights in daylighting zone (C405.2.1.1.3).
●In case the total wattage of general lighting in the daylighting zone is more than 150 watts, daylight-responsive control is required. This is achieved by using a DIM-24 sensor in the daylighting zone set to constant lighting to dim lights continuously from full light output to 15 percent of full light output or lower (C405.2.3).
IR Quattro HD DIM-24 、 TR 100 、 US Hallway DIM-24 、 US Oneway DIM-24* 、 LV-1-W 、 LV-2-W 、 DT Quattro DIM-24 |
|
[ Private Office ][ Meeting Room ][ Open Office ][ Reception ][ Lobby ][ Corridor ] |
|
Application note & Design Guide |
|
|
|
Please see the document for details |
|
|
|
|
|
|
|