How do I access a single Modbus RTU/ASCII slave device from two Modbus RTU/ASCII master devices
●Follow the procedure described below to configure the tGW-725 module:
■Step 1: Confirm that both the Ethernet connection and the tGW-700 series module are functioning correctly. For detailed information regarding how to install, configure and operate your tGW-700 series module, refer to the tGW-700 Quick Start Guide
■Step 2: Execute the eSearch Utility to search for any tGW-700 modules connected to the network, and then click the name of the tGW-725 module to select it.
■Step 3: Click the “Web” button to log in to the web configuration pages for the tGW-725 module (use the default password “admin”), or enter the URL address of the tGW-725 in the address bar of the browser.
■Step 4: Click the “Port1” tab to display the Port1 Settings page.
■Step 5: Select the appropriate Baud Rate, Data Format and Modbus Protocol settings from the relevant drop down options. The following is an example: Baud Rate (bps) “9600”, Data Size (bits) “8”, Parity “None”, Stop Bits (bits) “1” and Modbus Protocol “Modbus RTU”.
■Step 6:In the Pair-connection settings area forPort1, check that the configuration details are the same as those shown in the table below
■Step 7:Amend any details as required and then click the “Submit”button to complete the configuration.
■Step 8: Click the “Port2” tab display the Port2 Settings page.
■Step 9: Select the appropriate Baud Rate, Data Format and Modbus Protocol settings from the relevant drop down options. The following is an example: Baud Rate (bps) “9600”, Data Size (bits) “8”, Parity “None”, Stop Bits (bits) “1” and Modbus Protocol “Modbus RTU”.
■Step 10:In the Pair-connection settings area for Port2, check that the configuration details are the same as those shown in the table below
■Step 11: Amend any details as required and then click the “Submit” button to complete the configuration.
■Step 12: Click the “Home” tab to confirm that the pair-connection settings for Port1 and Port2 are correct.
●Follow the procedure described below to configure the tGW-715 module:
■Step 13: In the eSearch Utility, click the name of the tGW-715 module to select it, and then click the “Web” button to log in to the web configuration pages for the tGW-715 module (use the default password “admin”), or enter the URL address of the tGW-715 in the address bar of the browser.
■Step 14: Click the “Port1” tab to display the Port1 Settings page.
■Step 15: Select the appropriate Baud Rate, Data Format and Modbus Protocol settings from the relevant drop down options. The following is an example: Baud Rate (bps) “9600”, Data Size (bits) “8”, Parity “None”, Stop Bits (bits) “1” and Modbus Protocol “Modbus RTU”.
■Step 16: In the Pair-connection settings area for Port1, select “Server” from the “Server Mode” drop down options
■Step 17: Click the “Submit” button to complete the configuration.
■Step 18:Clickthe “Home”tab to confirm that the pair-connection settings forPort1 are correct.