TPC 4000-D ASSY 2481 ENGINEERING DIAGRAM

2022-03-07
●RACK MOUNTED STEEL CHASSIS ZINC PLATED
▲19" STANDARD WIDTH, RACK MOUNTING. 1.72" HEIGHT 12" DEPTH
●INPUT: 120/208VAC, 3-PHASE WYE, 50/60 HZ.
▲30 AMP / PHASE MAXIMUM TOTAL CURRENT.
▲24 AMP / PHASE TOTAL CURRENT (DE-RATED).
▲CABLE: 10/5 CABLE, 15 FT. LONG.
▲PLUG: NEMAL21-30PPLUG.
●OUTPUT: 10 NEMA 5-20R RECEPTACLES
▲3 SWITCHED PER PHASE, ACTIVATED BY LOCAL-OFF-REMOTE ROCKER
▲1 UNSWITCHED, ON WHEN MAIN CIRCUIT BREAKER IS ON.
●CIRCUIT BREAKERS: 1 MAIN, 3-POLE, 32 AMP MAGNETIC WITH GUARD.
▲7 BRANCH, 1-POLE, 20 AMPTHERMAL RESETTABLE.
●INDICATOR LIGHTS: 1 GREEN, ON WHEN CIRCUIT BREAKER IS ON
▲3 GREEN, ON WHEN SWITCHED SECTION IS ON
●FILTER: EMI/RFI, 30AMP RATING, 50/60 HZ.
▲COMMON MODE, LINE TO GROUND DIFFERENTIAL MODE, LINE TO LINE
●REMOTE I/O SWITCHING CONNECTOR, 3 EACH.
▲MATES WITH AMP # 1 -480305-0 CONNECTOR WITH AMP #60620-1 PINS.

Eaton

TPC 4000-D

More

Part#

RACK PDU

More

More

Outline Dimension Drawing

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

21 MAR 03

REV D

TPC_4000_D_2481D_ME