Horizontal A.C. Motors Totally Enclosed Fan Cooled Enclosure Fire Pump Motors
■On May 14, 2013, Nidec Motor Corporation expanded its UL Listed Fire Pump Motor file (EX5189) to include inverter duty (10:1 variable torque), 500HP or less, and frame sizes 143-5012.
■For Nidec Motor Corporation to be able to apply the UL Listed Fire Pump label, motors must meet the following requirements:
●Designed to meet NEMA®† Design "B" parameters per NEMA®† MG1-2014
●Calculated Safe Stall Time must exceed 12 seconds (cold) / 8 seconds (hot)
●Motors designated for Canada must meet CSA-390 Table 2 efficiency values
●600V or less
●500HP and lower
●5012 frame and smaller
●1.15 service factor (max)