How to troubleshoot communication problem on RS-485 network FAQ

2022-01-27
●Problem phenomenon:
■Communication failed with remote I/O modules/units.
■Using the other brand RS-485 converter (not ICP DAS converter).
■Users’ tools or programs sometimes meet communication problem such as failed to read
data or timeout error.
●ICP DAS Remote I/O modules/units need pull high and pull low resistors for stable signal on the RS-485 network. If the impendence does not match with requirement, the signal on RS-485 may become unstable as below. It will cause communication problems.
●Below are some suggestions to solve the problem:
■Use ICP DAS converter: ICP DAS converter comes with pull high and pull low resistors. Itcan stable the communication signal on RS-485 network.
■Add pull high and pull low resistors: Users can add pull high and pull low resistors on RS-485 network for stable communication signal
■Add tM-SG4:
▲tM-SG4 comes with pull high and pull low resistors. It also can stable communication signal on RS-485 network.