How to configure a large amount of the same modules with same configurations in INIT* to GND state
●DCON Utility Pro provides a very quick and easy way to finish this job.
■Step 1: Select the “Remote I/O INIT* Quick Configuration” -> “Configure as INIT* Status” ->Select tM option -> then tAD4P2C2 module ID.
■Step 2: Select the AD 4~20mA type code for channel 0 then “Set all channels as CH0”
■Step 3: Set the Protocol as Modbus RTU, Address 1, Baud Rate 19200
■Step 4: Turn off the power and remove the previous configured tAD4P2C2 and let the INIT* in normal state.
■Step 5: Connect the next tAD4P2C2 in INIT* to GND state and turn on the power.
■Step 6: Change the Address and “Write Configurations to I/O Module”.
■Step 7: Repeat the Step 4 to Step 6.
■Step 8: After finish all modules, we can create the folder for each application and save the configurations to file.
■Step 9: It can load the previous configured file to review the module’s setting and write to module.
|
|