GW-7552 and SIMATIC STEP 7(TIA Portal)Configurations
●Select “Create new project”;Set project name and click “Create”
●Select “Configure a device”
●Select ”Add new device”;Selectyour PLC type and click “Add”
●Click “Options”and then click “Install general station description file(GSD)”
●Click “...”;Select the directory of GW-7552’s GSD file(ipds0b87.gsd) and click”OK”
●Tick the item of GW-7552 GSD file
■Click “Install” and then click “Yes”
●Click “close”
●Click ”Overview” and then click “Device Configuration”
●Click “Network view” and confirm GW-7552 is available in “Catalog”
■The path of GW-7552in “Catalog” :
▲“Other field devices”→“PROFIBUS DP” →“Gateways” →“ICP DAS Co. Ltd” →”GW-7552”
●Double click “GW-7552”
■hold down the block which is PROFIBUS DP interface in PLC and move the mouse cursor to the block of GW-7552.
●Click “PLC_1 DP-Mastersystem(1)”
■click “Properties”
■click ”PROFIBUS”
■In “Network settings”
▲set”Highest PROFIBUS address”=126,“Profile”=DP.
▲“Transmission speed” : set the value which you need.
●If “Not assigned” is showninGW-7552, click ”Not assigned”and select your PLC.
■Double Click your PLC
●Click the PROFIBUS DP interface.
■Click “Properties” and “PROFIBUSaddress”
■In”Parameters”:
▲set “Interface type”=PROFIBUS.
▲ ”Address”: set PROFIBUS address for your PLC.
●Select “Slave_1”(If GW-7552 is “Slave_2”, select “Slave_2”,etc.)
■Click “Properties” and “Device-specific”
■You can set device parametersof GW-7552in “Device-specific parameters”(e.g. baud rate, parity, data bit)
●Click “PROFIBUS address”
■You can set PROFIBUS address of GW-7552 in “PROFIBUS address”
●Double click “System module” and any IO module which you need.
■Click the IO module and “Properties” and “Device-specific”
■You can set the module parameters in “Device-specific parameters”
●Click “Topology view”
■Click your PLC
■Click “Save project”
■Click “compile” and “Download to Device”
●Select your PG/PC interface
■If PC connects PLC successful,the background will be orange
■Click “Load”
●Click “Load”
●Tick “Start all” and click “Finish”
●Click ”Go online”
■Click “Start CPU”
|
|
|
|