SE-601 DC GROUND-FAULT PROTECTION WITH ASYMMETRICAL SE-GRM Technical Note
●An asymmetrical ground reference can assist in troubleshooting, as both the polarity and magnitude of the bus voltage are different. For example, a 75:25 ratio results in +94 V and -31 V to ground on a 125-V system.
●An SE-601 and SE-GRM can be used in an asymmetrical-ground-reference application. An SE-GRM125 contains two 5-kΩ resistors. To create a 75:25 ratio, install a 10-kΩ 5-Watt resistor in series with the SE-GRM125.
|
|