Rosemount™ Tank Gauging Accessories for tank gauging systems

2021-10-26
●Accessories for the Rosemount Tank Gauging system, including:
■Tankbus FF terminator;
■Tankbus FF coupler;
■Rosemount 2180 Field Bus Modem;
■Rosemount 3180 Enraf® Bus Modem;
■Safety switch.
●Overview:
■Tankbus FF terminator:
◆A Tankbus terminator is required at the end of the Tankbus. The external Tankbus terminator eliminates signal reflections at theend of the cable and converts the tankbus signal transmitted as a current into a voltage, which is detectable by all devices.There is no need for a separate bus terminator if a Rosemount 2230 Graphical Field Display, Rosemount 2240S Multi-inputTemperature Transmitter, or Rosemount 5900S Radar Level Gauge is the last device on the bus.
■Tankbus FF coupler:
◆The 6-channel Tankbus segment coupler is designed for FOUNDATION™ Fieldbus systems and is Entity and FISCO compliant. It includes adjustable spur short circuit protection and an integrated switchable bus termination. The segment coupler is typically used as a junction box to distribute the Tankbus to multiple tanks and/or transmitters.
◆The spur circuit protection maximum current limitation is selected for all channels via a rotary switch. Different current values, 30,35, 45 and 60 mA, can be selected, which allows all Rosemount tank gauging devices to be connected and protected.
■Rosemount 2180 Field Bus Modem:
◆The Rosemount 2180 Field Bus Modem (FBM) is used for connecting a TankMaster PC to the TRL2 communication bus. The Rosemount 2180 is connected to the PC using either the USB or the RS232 interface.
◆The field bus modem has LEDs to indicate power-on and communication, and if required front panel switches to set gain and termination. The modem is fitted on a standard DIN rail with the mounting kit included in all deliveries.
◆The Rosemount 2180 is delivered with cables for RS232 and USB connection. The USB cable also supplies power to the modem. A separately power supply cable (included in delivery) is only necessary for the RS232 option.
■Rosemount 3180 Enraf® Bus Modem:
◆When an Enraf gauge is replaced with a Rosemount radar gauge using emulation, it is necessary to configure the Rosemount gauge for emulation. Configuration is made with the WinSetup software and requires a Rosemount 3180 Enraf Bus Modem. How the procedure is done depends on the system type.
◆The 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the Rosemount TankMaster Inventory Software
■Safety switch:
◆The safety switch is an explosion proof circuit breaker between the power source and the Rosemount 2410 Tank Hub. The switch is recommended to ensure that power is disconnected during service.

EMERSON

05900-1000-000205900-1000-0001FBM 2180EBM 318005900-1000-0003

More

Part#

Accessories for tank gauging systems

More

More

Datasheet

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

July 2021

Rev AD

00813-0100-5101

5.6 MB

- The full preview is over. If you want to read the whole 28 page document,please Sign in/Register -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.

Contact Us

Email: