Belimo Energy Valve™ INSTRUCTION MANUAL

2021-10-15
●INSTALLATION
■Inlet Length:The Energy Valve requires a section of straight pipe on the valve inlet to guarantee sensor accuracy. This section should beat least 5 pipe diameters long with respect to the size of the valve.
◆½” [DN15] 5 x nominal pipe size = 2½” [64 mm]
◆¾” [DN20] 5 x nominal pipe size = 3¾” [95 mm]
◆1” [DN25] 5 x nominal pipe size = 5” [127 mm]
◆1¼” [DN32] 5 x nominal pipe size = 6¼” [159 mm]
◆1½” [DN40] 5 x nominal pipe size = 7½” [191 mm]
◆2” [DN50] 5 x nominal pipe size = 10” [254 mm]
■Outlet Length:No requirements for outlet length. Elbows can be installed directly after the valve.
●PIPING
■The Energy Valve is recommended to be installed on the return side of the coil. For ½” through 2” valves both temperature sensors are remote and are supplied withfemale NPT threaded pipe body. The (T2) sensor should be installed in the direction of fl ow after the actuator. The (T1) sensor should be installed on the other side of the coil. P/T ports are recommended on both sides of the valve and the supply side of heat transfer device to allow for pressure, fl ow measurement, and calculation.
■It is not necessary to install one strainer per unit. Belimo recommends installing one strainer per system. If the system has multiple branches, it is recommended to install one strainer per branch.

Belimo

Energy Valve

More

More

User's Guide

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

2019/06/02

71610-00001.B

1.3 MB

- The full preview is over,the data is 2 pages -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.

Contact Us

Email: