TB-D5016-TRI-010 SIL 3 Termination Board 16 positions for Tricon CX Universal card 3902X

2021-09-17
The TB-D5016-TRI-010 Termination Board provides direct connection between the Tricon CX Universal card 3902X and D5000 / D6000 series modules.
The 24 Vdc Power Supply of the TB is given by OR-ing diode mixing of two supply sources (PWR1 & PWR2) with related plug-in terminal blocks, for a redundant power supply.
The 24 Vdc is used to supply D5000 / D6000 series modules by TB connector and it is given to Tricon CX Universal card 3902X to drive or control AI, AO, DI or DO module loop (with DTT De-energized To Trip condition of the loop). In the diagram is shown a TB-D5016-TRI-010 channel connected to AI, AO, DI or DO single channel module by means of TMR voter of the Tricon CX Universal card 3902X.

GM INTERNATIONAL

TB-D5016-TRI-010

More

Part#

Termination Board

More

More

User's Guide

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

2021/07/24

ISM0385-0

330 KB

- The full preview is over. If you want to read the whole 4 page document,please Sign in/Register -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.