HiD2082 Temperature Converter
■This isolated barrier is used for intrinsic safety applications.
This device accepts thermocouples (TC), millivolts,potentiometers, or resistance temperature detectors (RTD) from a hazardous area and converts them to an isolated, linearized analog output in the safe area.
The outputs can be selected as a current source, current sink, or voltage source with DIP switches on the side panel.
The device can also be configured as a signal splitter.
Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus. The fault conditions are monitored via a Fault Indication Board.
The device is easily configured by the use of the PACTware configuration software.
This device mounts on a HiD Termination Board.
●2-channel isolated barrier
●24 V DC supply (bus powered)
●Thermocouple, RTD or potentiometer input
●Usable as signal splitter (1 input and 2 outputs)
●Linearized output 4 mA ... 20 mA, sink/source or 1 V ... 5 V
●Sensor breakage detection
●Configurable by PACTware
●Line fault detection (LFD)
●Up to SIL 2 acc. to IEC 61508/IEC 61511