AQB-L803 Circuit Breaker Time / Current Curves (Phase Current)

2021-05-07
●Notes:
●Curve accuracy applies from -20 C to +55 C ambient. For possible continuous ampere derating for ambient above 50 C, refer to the Eaton Corporation.
●For high fault current level, a fixed Instantaneous Override is provided at 14,400A.(tolerance ±20%)
●The end of the curve is determined by the interrupting rating of the circuit breaker.
●The AQB - L803 is suitable for functional field testing with Test Kit (Catalog # STK2).
●Calibration response in Short Delay Pickup range is the same for one, two or three poles in series.
●There are memory effects that can act to shorten the Long Delay. The memory effects come into play if a current above the Long Delay Pickup value exists for atime and then is cleared by the tripping of a downstream device or the circuit breaker itself.
A subsequent overload will cause the circuit breaker to trip in a shorter time thannormal. The amount of time delay reduction is inverse to the amount of time thathas elapsed since the previous overload.
Approximately five minutes are required between overloads to completelyreset the memory

Eaton Bussmann

AQB-L803

More

Part#

Circuit Breaker

More

More

Technical Documentation

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

2008 July

TC01208006E

94 KB

- The full preview is over,the data is 1 pages -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.

Contact Us

Email: