FK 9105 Approved for intrinsic fire resistance, material: Sheet steel
●Cable junction box 1.5-4 mm², Cu
●Connection box 1.5-10 mm², Cu
●5-pole per pole4x 1.5 mm² sol, 4x 2.5 mm-sol, 4x 4 mm² sol, 2x 6 mm² sol, 2x 10 mm² sol
●connecting terminal made from ceramic with resistance to high temperatures
●mounted grommets 4 EDKF 32, sealing range: Ø 8-23 mm, closed
●intrinsic fire resistance in accordance with DIN 4102 Part 12 (German standard) in combination with function-retaining cables
●tested with cable manufacturers Dätwyler, Eupen, Nexans, Studer, Pirelli and Lynenwerk for the intrinsic fire resistance E30 and E90, see test certificate no.: P-MPA-E-02-032, valid till 20 March 2023, download available from www.hensel- electric.de
●tested for insulation integrity PH120 in accordance with BS EN 50200 in connection with insulation retaining cables, see test certificate, download available from www.hensel-electric.de > type - documents
●mounted using exterior wall fixings, bore hole 8.2 mm(for dowels refer to technical data)
●for normal environment and protected outdoor
●colour: orange, RAL 2003
|
|