PFC-6030 FIRE ALARM CONTROL PANEL

2022-10-20

●Description
■The PFC-6030 is a versatile thirty point analog/addressable fire alarm control panel that utilizes the Potter/Nohmi device protocol that has a complete line of initiating and control devices. The SLC is capable of 50 ohms of resistance and does not require the use of twisted or shielded wire. The thirty (30) points may be any combination of smoke sensors, heat detectors or modules.
■The PFC-6030 has a metal cabinet with a key lock and a dead front standard. The cabinet will house 8 Ah or 18 Ah batteries. The large viewing window allows easy viewing of the LCD and the standard LEDs. The keypad allows easy operation and navigation of the system menu.
■All of the outputs are power limited, are power regulated and may be programmed for Potter/AMSECO, Gentex®, CooperWheelock® and System Sensor® strobe synchronization. The outputs may be configured for any combination of strobe brands and all will sync. The outputs also may be configured for door holder power, auxiliary power and constant power.
■The panel has auto-programming learn mode that will not affect the existing system when adding or deleting a device. The system is capable of 99 software zones, cross zoning and counting zones. The panel is fully programmed from a PC based software program that will work with Microsoft XP, Vista or Windows 7.0 operating systems.
■The PFC-6030 has an Ethernet connection for programming network connectivity and IP reporting communicator. The system uses a simple patch cable for connecting a PC to the panel. In addition, the system may be connected to a building network and programmed while on the network. The system has a built in e-mail function and will send system E-mail reminders. The IP communicator is listed with the Sur-Gard III IP receiver.
■The panel will support P-Link devices which include: the RA-6075, RA-6500 and LED-16 Annunciators, RLY 5 Relay Module, SPG-1000 Serial Parallel Gateway (printer card), an FCB-1000 Remote Ethernet/IP connection, DRV-50 LED driver for 50 LEDs, PSN-1000 Remote Power Supplies (10 Amp) and FIB-1000 P-Link Fiber Interface Module. In addition, the panel allows for the installation of the UD-1000 dual line telephone line digital alarm communicator transmitter (DACT). The UD-1000 is programmable for a single line or dual line and is compatible with Ademco's Contact ID or SIA DCS protocols.
■The complete system may be converted to Class A with a CA-6075 module. The CA-6075 provides the hardware necessary to convert the remote annunciators through the Potter P-Link connection protocol, the NACs and the SLC to Class A operation.
●Features
■30 Analog/Addressable Points in Any Combination
■3.5 Amp Power Supply
■2 NACS, Regulated, Rated at 3 Amps each
■Strobe Synchronization and System Wide Sync for Potter/AMSECO®, Gentex®, Cooper Wheelock® and System Sensor® strobes
■System Wide Class A or B
■99 Software Zones
■Large LCD and Keypad for Ease of Operation
■Cabinet will house 8 or 18 Ah batteries. Dead Front Cabinet for Clean Look
■Smoke Detector Drift Compensation and Maintenance Alerts
■NFPA 72 Compliant Smoke Sensitivity Test Built-In
■1,000 Event History Buffer
■Optional two line DACT with UD-1000 that can report General, Zone, or Point
■P-Link Communication Line for Annunciators and Accessories
■E-Mail System Status, Reports and Event Information
■Integrated, listed IP Communicator
■Ethernet Port for Programming and Network Connectivity

POTTER

PFC-6030PSAPSHAFHARHADDAAB-6AB-4AIBARBASBMCMAPS-SAAPS-DASCM-4DCM-4TRM-4MOM-4CIZM-4SCIRA-6075RA-6500LED-16PSN-1000RLY-5SPG-1000FCB-1000FIB-1000CSCHSS-24HS-24CO-12CO-24UD-1000AE-8CA-6075SLCP32-1T

More

Part#

FIRE ALARM CONTROL PANEL

More

More

Datasheet

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

11/13

REV A

1.2 MB

- The full preview is over. If you want to read the whole 3 page document,please Sign in/Register -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.

Contact Us

Email: