CT-11: FPL ZERO-SEQUENCE SENSORS WITH LITTELFUSE RELAYS Technical Note

2020-11-16

Toroidal (Type T) zero-sequence sensors manufactured by Federal Pioneer Ltd. can be used with Littelfuse Startco ground-fault and motor-protection relays. Table 1 lists compatible FPL sensors and window sizes. These sensors can be used on resistance-grounded systems and on solidly grounded systems where the maximum ground-fault current is less than 50 kA.
When using an FPL sensor with the SE-701 Ground-Fault Monitor, the CT-primary rating is 50 A. The SE-701 set-point range is 1 to 99% in 1% increments, which corresponds to 0.5 to 49.5 A in 0.5-A steps. If the ground-fault current can exceed 400 A, a voltage-clamping device must be used as shown in Fig. 1. An SE-EFVC is recommended for these applications.
When using an FPL sensor with an FPS, FPU-32, MPS, or MPU-32, the earth-fault CT-primary rating should be set to 50 A. This will provide correct earth-leakage metering information and trip levels. The set-point range is 1 to 100% in 1% increments, which corresponds to 0.5 to 50 A in 0.5-A steps. For the MPS, the set-point range is 5 to 100% in 1% increments, which corresponds to 2.5 to 50 A in 0.5-A increments.If the earth-fault current can exceed 200 A, a voltage-clamping device must be used. An SE-EFVC is recommended for these applications, as shown in Figs. 2, 3a, and 3b.

Littelfuse

FPU-32MPU-32MPU-CIMFPS-CTUMPS-CTU

More

Part#

FPL ZERO-SEQUENCE SENSORS

More

More

Application note & Design Guide

More

More

Please see the document for details

More

More

English Chinese Chinese and English Japanese

2019/03/29

Rev: 111418

Pub. TN-CT11

324 KB

- The full preview is over. If you want to read the whole 3 page document,please Sign in/Register -
  • +1 Like
  • Add to Favorites

Recommend

All reproduced articles on this site are for the purpose of conveying more information and clearly indicate the source. If media or individuals who do not want to be reproduced can contact us, which will be deleted.

Contact Us

Email: