Honeywell Pressure Switches
Rev. D 50038194
OVERPRESSURE
, CAUTION
PRODUCT DAMAGE
• Do not exceed the operating pressure.
Failure to comply with these instructions could result in
death or serious injury.
If the operating pressure is exceeded, the life of the Honeywell
pressure switch may be reduced and electrical failure may
occur. Both static and dynamic over-pressuring must be
considered, particularly in hydraulic system applications.
Hydraulic pressure fluctuations can have very high and rapid
pressure spikes, as in a water hammer effect. The high pressure
versions (HP Series, HE Series) have a snubber feature built-in
to reduce the peak pressure applied to the pressure switch. The
medium and low pressure versions (ME Series, LP Series, LE
Series) do not employ this feature.
If system pressure pulses are expected, choose a pressure
switch with a proof pressure rating high enough to allow
operation at the highest expected pressure spikes.
MEDIA COMPATIBILITY
, CAUTION
PRODUCT DAMAGE
• Use non-abrasive, chemically compatible media to pre-
vent damage to the pressure switch.
Failure to comply with these instructions could result in
death or serious injury.
The pressure switch’s fluid path is an assembly of zinc-
plated steel, stainless steel, DuPont™ Teflon
®
-coated Kapton
®
,
and nitrite. The Series is compatible with a wide variety of
petroleum-based fluids, air, water, and mineral oil-based brake
fluid. Please confirm your media compatibility or speak with a
Honeywell Application Engineer.
WIRING INSTRUCTIONS
NOTICE
To ensure proper environmental sealing and electrical
connections when using a connector, follow the connector
manufacturer’s installation guidelines. All terminal cavities
must be sealed using the correct wire gauge and seal com-
bination. If only two leads are used, any additional terminal
cavities should be sealed per the connector manufacturer’s
installation guide. Honeywell recommends using a crimping
tool for crimping wires to the connector terminals. Contact
the individual connector manufacturer for connector wiring.
FUNCTIONAL TEST
Connect the pressure switch to the pressure source (off).
Based on the pressure switch’s specified normally open (NO) or
normally closed (NC) output, connect the electrical termination
to a dc voltage supply. With no pressure on the pressure switch,
turn on the power supply and ensure that the pressure switch
is in the correct NO or NC position. Apply the appropriate set
point pressure to ensure that the NO or NC contact position of
the switch will switch over.