AUTOMATIC TRANSFER SWITCH
CONTROLLERS ATL SERIES
The automatic transfer switch controllers ATL 600 - ATL601 - ATL 610 - ATL 800
can supervise and manage the changeover between 2 three-phase power sources.
The voltage and frequency measurements are shown on the graphic LCD display and
the LEDs on the front panel provide a clear indication about the power source status.
Operational characteristics ATL 600 ATL 601 ATL 610 ATL 800
Power supply voltage 110-240VAC 12/24VDC 110-240VAC and 12/24VDC 110-240VAC and 12/24/48VDC
Voltage measurement inputs
• Rated voltage Ue 100-480VAC L-L 100-480VAC L-L 100-600VAC L-L
• Measurement range 50-576VAC L-L 50-576VAC L-L 50-720VAC L-L
• Frequency range 45...65Hz
Current inputs - - -
Programmable digital inputs 6 6 8
•Type of input Negative
Programmable relay outputs 7
5 with 1 normally open contact each (NO - SPST) rated 8A 250VAC
2 with 1 changeover contact each (NO/NC - SPDT) rated 8A 250VAC
Expandability - With EXP... modules (2 max.) With EXP... modules (3 max.)
RS485 port - With EXP 1012 Built-in
Real time clock - With EXP 1012 Built-in
Compatible software and APP
,
and APP
, ,
and APP
Flush-mount housing 144x144mm 144x144mm 180x240mm
Degree of protection IP20 at rear. IP40 on front; IP20 at rear.
IP65 with EXP80 01 optional gasket
IP65 on front
2 power sources automatic
transfer switch controllers
Certifications and compliance
Certifications obtained:
cULus, EAC, RCM.
Compliant with standards: IEC/EN 61010-1, IEC/EN 61010-2-030,
IEC/EN 61000-6-2, IEC/EN 61000-6-4, IEC/EN 60947-1,
IEC/EN 60947-6-1,UL508, CSA C22.2 n°14.
Management of 2 power sources
Control of undervoltage, overvoltage, phase loss, asymmetry,
minimum and maximum frequency, with time delay and
independent enabling
Inputs, outputs, limits, counters and alarms are
programmable by the user
Power sources can be independently defined as
utility or generator
Automatic test management for standby and
rotation generators
Suitable for LV and MV systems
Programmable maintenance alarms
Suitable for contactors, motorised circuit breakers
and motorised changeover switches
Tie breaker management for ATL 800 only
Closed transition available for ATL 800 only
Customizable change-over devices layout and
transfer strategy for ATL 800 only
Built-in PLC technology for ATL 800 only
Built-in NFC technology for ATL 800 only.
ATL 6... ATL 800 - Some possible configurations
For ATL 610 - ATL 800 only:
Dual AC/DC power supply
Real time clock with backup energy
Expandability with EXP... modules (e.g. Ethernet, extra I/Os).