Data sheet
Remote-I/O - u-remote
UR20-FBC-PL
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date March 23, 2018 7:49:33 AM CET
Catalogue status 09.03.2018 / We reserve the right to make technical changes. 2
Dimensions and weights
Width 52 mm
Width (inches) 2.047 inch
Height 120 mm
Height (inches) 4.724 inch
Depth 76 mm
Depth (inches) 2.992 inch
Mounting dimension - height 128 mm
Net weight 318 g
Temperatures
Operating temperature -20 °C ... +60 °C
Storage temperature -40 °C ... +85 °C
Connection data
Type of connection
PUSH IN
Wire connection cross section, finely
stranded, max. 1.5 mm²
Wire connection cross-section, finely
stranded, min. 0.14 mm²
Wire cross-section, finely stranded, max.
(AWG) AWG 16
Wire cross-section, finely stranded, min.
(AWG) AWG 26
Wire cross-section, solid, max.
1.5 mm²
Wire cross-section, solid, max. (AWG) AWG 16
Wire cross-section, solid, min.
0.14 mm²
Wire cross-section, solid, min. (AWG) AWG 26
General data
Air humidity (operation) 10% to 95%, non-
condensing as per DIN EN
61131-2
Air humidity (storage) 10% to 95%, non-
condensing as per DIN EN
61131-2
Air humidity (transport) 10% to 95%, non-
condensing as per DIN EN
61131-2
Air pressure (operation)
≥ 795 hPa (height ≤ 2000
m) as per DIN EN 61131-2
Air pressure (storage) 1013 hPa (height 0 m) to
700 hPa (height 3000 m)
as per DIN EN 61131-2
Air pressure (transport) 1013 hPa (height 0 m) to
700 hPa (height 3000 m)
as per DIN EN 61131-2
Pollution severity
2
Shock 15 g über 11 ms, halbe
Sinuswelle, gem. IEC
60068-2-27
Surge voltage category II
Test voltage 500 V
UL 94 flammability rating
V-0
Vibration resistance 5 Hz ≤ f ≤ 8.4 Hz: 3.5
mm amplitude as per IEC
60068-2-6, 8.4 Hz ≤ f ≤
150 Hz: 1 g acceleration
as per IEC 60068-2-6
Power supply
Current consumption from I
IN
(power
segment of the field bus coupler), typ. 100 mA
Feed current for I
IN
(input current path) ,
max. 10 A
Feed current for I
OUT
(output current
path) , max. 10 A
Feed current for the system, max.
4 A
Supply voltage 24 V DC +20%/ -15%, via
the system bus
Supply voltage for outputs
24 V DC +20%/ -15%
Supply voltage system and inputs 24 V DC +20%/ -15%