MULTI MULTI MEASURING INSTRUMENTS CO., LTD
Akihabara Murai Bldg. 7F, 1-26 Kanda Sakuma-cho, Chiyoda-ku, Tokyo 101-0025, Japan
TEL: +81-3-3251-7013 FAX: +81-3-3253-4278 E-mail: multi@multimic.com
Home Page: http://www.multimic.com/
MULTI CIRCUIT DC CURRENT MONITOR (16 CHANNELS)
Model MCM-1600PV
Measuringdisplay of DC current values generated by PV systems and DC load
current of related apparatus in multi circuit successively for a long term as well as
memorizing the average current values between the intervals, of which data can be
transmitted to PC in Excel File.
The circuits to be measured are max. 16 lines and in PV systems, can measure DC
current per each string unit at the same time.
Using clamp type current sensors which enable safe and easy operation.
MEASUREMEMORIZEDISPLAY THE DC CURRENT OF MAX.16 CIRCUITS AT THE
SAME TIME
EASY FOR DATA MANAGEMENT (STORAGE BY CSV FORMULA)
GENERAL
1. MEASURING FUNCTION
By Connecting Optional CT Sensors, the instrument can measure and memorize DC
current of 16 circuits at the same time and the memorized data can be seen even during
measurement.
2. LOGGING MEASURING FUNCTION
This instrument displays and memorizes the average current between the selected
intervals.
Interval : 1 / 5 / 10 / 15 / 30 / 60 minutes
Contents of Memory : Measuring Time / Measuring Circuit / The average current value
Capacity of Memory : Approx. 20,000 data (72 days with 5 minutes interval)
3. OTHER FUNCTION
Over Range Indication
: OL mark on LCD
Low Battery Indication
: B mark on LCD
Logging Mode Indication
: R mark on LCD
Auto Power Off
: Approx. 10 minutes after last key operation (this
function will not be active in case of using AC adapter,
timer set on and logging mode)
Contrast Adjustment
: by adjustment knob
Display of Battery Charge
: Rapid Charging = Red Lamp, Trickle Charge = Green
SPECIFICATIONS
Number of Measuring Circuit
: 16 circuits (channels)
Detection Method
: Clamp-on CT method
Measuring Range
: DC 0~99.9A
Minimum Resolution
: 0.1A
Measuring Accuracy
:±3%rdg±5dgt
Sampling
: Approx. 20mS
Measuring Temperature
: 050, less than 80%RH w/o condensing
Storage Temperature
: -1060, less than 80%RH w/o condensing
Measuring Circuit Voltage
: less than DC600V (insulated conductor)
Insulation Resistance
: more than 100M Ω by DC500V insulation
tester(between input terminal and housing case) more
than 50M Ω by DC500V insulation tester (between
power supply source and housing case)
Withstanding Voltage
: AC2200V (50 / 60Hz) one minute between power
supply source and housing case
Power Supply
: AC100V240V with adapter
Internal Ni-hydride Battery
Battery Life
: Approx. 4 days at continuous use by full charge
Dimensions & Weight
: 236(W) x 170(H) x 56(D)mm, approx. 840gs
Standard Accessories
: Carrying Case, AC Adapter, USB Cable, Instruction
Manual
Optional Accessories
: Clamp CT with i.d. 30mm & 2.8m cable, CT Carrying
Case (for max. 8 CTs)