© 2022 Littelfuse, Inc.
Littelfuse.com/Fuses
POWR-GARD
®
FUSE
Selection Guide
UL CLASS
LITTELFUSE
SERIES
OVERLOAD
CHARACTERISTICS
AC RATINGS DC RATINGS
RECOMMENDED
ACCESSORIES
VOLTAGE
(VOLTS)
CURRENT
(AMPERES)
INTERRUPTING
(AMPERES)
VOLTAGE
(VOLTS)
CURRENT
(AMPERES)
INTERRUPTING
(AMPERES)
L
KLPC Time-Delay 600 200–6000 200 K/300 K* 480 200–6000 20,000*
–
KLLU Time-Delay 600 601–4000 200,000 300 601–4000 20,000*
LDC Fast-Acting 600 150–2000 200,000 600 150–2000 50,000
RK1
LLNRK Time-Delay 250 0.1–600
200 K/300 K*
125 0.1–600
20,000*
LFR25
LLSRK_ID Time-Delay 600 0.1–600 300 0.1–600 LFR60
LLSRK Time-Delay 600 0.1–600 300 0.1–600 LFR60
KLNR Fast-Acting 250 1–600
200,000
125 1–600 LFR25
KLSR Fast-Acting 600 1–600
250
300
1–30
35–600
LFR60
RK5
FLNR_ID
Time-Delay
250 35–600
200 K/300 K*
125 35–600
20,000
LFR25
FLNR 250 0.1–600 125 0.1–600
FLSR_ID 600 0.1–600 300 0.1–600
LFR60
FLSR 600 0.1–600 300 0.1–600
IDSR 600 0.1–600 600 0.1–600
J
JTD_ID Time-Delay 600 0.8–600
200 K/300 K*
300 0.8–100
20,000*
LFJ60 • LFPSJ
JTD Time-Delay 600 0.8–600 500 110–600
JLS Fast-Acting 600 1–600 200,000 – – –
T
JLLN
Fast-Acting
300 1–1200
200,000
160
125
1–60
70–1200
20 K (1–30 A)*
20 K (35–1200 A)
LFT30 • LSCR
(700–800 A)
JLLS 600 1–1200 300 1–1200 20 K (1–1200 A)*
LFT60 • LSCR
(700–800 A)
CC
CCMR Time-Delay 600 0.2–30 200 K/300 K*
300
500
2/10–10
12–30
20,000*
L60030C
LFPSC
LPSC • 571
572
LEC • LEY
KLDR Time-Delay 600 0.1–30 200,000 300 0.1–30
KLKR Fast-Acting 600 0.1–30 200,000 300 0.1–30
CD
CCMR Time-Delay 600 35–60 200 K/300 K* 250 35–60 20,000* LFC60060
G
SLC Time-Lag
600
480
0.5–20
25–60
100,000 170 0.5–60 10,000*
LFG600 (½–20 A)
LFG480 (25–60 A)
K5
NLN
Fast-Acting
250 1–600
50,000
250 1–600
20 K (1–60 A)
50 K (70–600 A)
LFH25
NLS 600 1–600
600
500
400
600
500
1–7
8–30
35–60
70–200
225–600
20 K (1–60 A)
50 K (70–600 A)
LFH60
* Littelfuse self-certied
FUSE CLASS AND SELECTION CHART
© 2022 Littelfuse, Inc.
Littelfuse.com/Fuses
POWR-GARD
®
FUSE
Selection Guide
UL CLASS
LITTELFUSE
SERIES
OVERLOAD
CHARACTERISTICS
AC RATINGS DC RATINGS
RECOMMENDED
ACCESSORIES
VOLTAGE
(VOLTS)
CURRENT
(AMPERES)
INTERRUPTING
(AMPERES)
VOLTAGE
(VOLTS)
CURRENT
(AMPERES)
INTERRUPTING
(AMPERES)
Midget
(Supplementary)
BLF Fast-Acting
250
125
0.5–15
20–30
10,000 – – –
L60030M
571 • 572
LEB • LEX •
LPSM
BLN Fast-Acting 250 1–30 10,000 – – –
BLS Fast-Acting
600
250
0.2–5
6–10
10,000 – – –
FLA Time-Delay 125 0.1–30 10,000 – – –
FLM Time-Delay 250 0.1–30 10,000 125 0.1–30 10,000*
FLQ Time-Delay 500 0.1–30 10,000 300 0.1–30 10,000*
KLK Fast-Acting 600 0.1–30 100 K/200 K* 500 0.1–30 50,000
KLKD Fast-Acting 600 0.1–30 100 K/200 K* 600 0.1–30 50,000
KLQ Time-Delay 600 1–6 10,000 – – –
FLU Fast-Acting 1000
0.44/
11
10,000
20,000
1000
0.44
11
10,000
20,000
LPHV
Solar
SPF
Solar (gPV)
– – – 1000 1–30
20,000 (1A–20 A)
50,000 (25–30 A)
LPHV
SPFJ 600 125–450 200,000 1000 70–450
20 K (70–200 A)
10 K (250–400 A)
20 K (450 A)
LFJ10 • LSCR
SPFI – – – 1000 2–30 20,000 Not Required
SPNH – – – 1500 50–400 30,000 LFNH
SPXV – – – 1500 1–60
50 K (1–20 A)*
50 K (25–30 A) SPXV-M
LFPXV
50 K (35–60 A) LFXV150
SPXI – – – 1500 1–32
30 K (1–20A)
30 K (1–20 A) SPXI-B
50 K (35–50 A)
50 K (35–60 A) SPXI-B
50 K (25–32 A) SPXI-M &
SPXI-BM
Not Required
SPXC – – – 1500 1–4 50,000*
High-Speed
L15S
Very Fast-Acting
150 1–1000 100,000
150
100
1–60
70–1000
20,000* LSCR • 1LFS
L25S 250 1–800
200,000
250
200
1–200
225–800
L50QS
500
35–800 500 35–800 50,000 LSCR
L50S 10–800 450 10–800 20,000
LSCR • 1LFS
L60S 600 1–800 – – –
L70QS 700 35–800 700 35–800 50,000 LSCR
L75QS – – 750 35–800 50,000 LSCR
L70S 700 10–800 – 650 10–800 20,000 LSCR • 1LFS
PSR 500–700 40–2250 200,000 450–600 40–2250 150,000 MS3H1000C
PSR 900–1300 50–1400 100,000 800–1000 50–1400 150,000 MS7H1500C
PSX – – – 1500 80–1400 250,000 MSXL2000C
Telecom
L17T
Fast-Acting
– – –
170
70–1200
100,000
LTFD Series
TLN – – – 1–600 LFR25
TLS – – – 1–125
LTFD101
LFT30060
(cartridge)
* Littelfuse self-certied
© 2022 Littelfuse, Inc.
Littelfuse.com/Fuses
POWR-GARD
®
FUSE
Selection Guide
CONDENSED CROSS REFERENCE GUIDE
This cross reference covers the most popular fuses for which there is a similar Littelfuse standard item. Furnished for your
convenience, it is meant to serve as a guide for product selection. We suggest you check all applicable specications before
making substitutions. For special applications, more complete information, and for fuse block and medium voltage fuse cross
referencing, visit Littelfuse.com or call 1-800-TEC-FUSE (1-800-832-3873).
COMPETITOR LITTELFUSE COMPETITOR LITTELFUSE COMPETITOR LITTELFUSE COMPETITOR LITTELFUSE
TLN NLN C519 229 JHC JTD_ID NOS NLS
10KOTS NLS C520 225 JHL LDFJ NRN NLN
50KOTN NLN CHSF L50QS JJN JLLN NRN (15-60A) NLKP
50KOTS NLS CJ JLS JJS JLLS NRS NLS
170M PSR CJS JLS JKS JLS OT NLN
A013F L15S CLF KLPC or KLLU KAA L15S OTM BLF or BLN
A015F L15S CLL KLLU or KLPC KAB L25S OTN NLN
A015R L15S CLU KLLU or KLPC KAC KLC OTS NLS
A025F L25S CM BLF KBH L50QS PC_UD PSR
A050F L50QS CRN-R FLNR_ID
‡
KLM KLKD PSC PSR
A060F L60S CRS-R FLSR_ID KLU KLLU or KLPC PV-(1-30)A10F SPF
A070F
L70QS CTN-R KLNR KN KLNR
PV-(50A-
200A)1XL15
SPNH
A13X L15S CTS-R KLSR KON NLN REN FLNR
+
A25X L25S
†
DCT SPF
†
KOS NLS RES FLSR
+
A2D-R LLNRK
§
DFJ LDFJ KRP-C KLPC RF FLNR
+
A2K-R KLNR EBS BLS KS KLSR RFA L15S
A3T JLLN ECNR FLNR_ID
‡
KTK KLK RFC KLC
A4BQ KLPC ECSR FLSR_ID KTKR KLKR RFL (750V) L70S (700 V)
A4BT KLLU or KLPC ERN FLNR
+
KTNR KLNR RFN (Mersen) FLNR
+
A4BY KLPC or KLLU ERS FLSR
+
KTSR KLSR RFS (Mersen) FLSR
+
A4J JLS FNA FLA KTU 601-2000A LDC RFV L50QS
A50P (type 1 & 4) L50QS FNM FLM KTU 2500-6000A KLPC RHN KLNR
A50QS L50QS FNQ FLQ LCL KLPC or KLLU RHS KLSR
A60X L60S FNQ-R KLDR LCU LDC S SOO
A6D-R LLSRK_ID
§
FRN-R FLNR_ID
‡
LENRK LLNRK SA SAO
A6K-R KLSR FRS-R FLSR_ID LESRK LLSRK_ID SC SLC
A6T JLLS FWA L15S
† §
LKU KLLU SEC SLC
A70P L70QS FWH L50QS LONRK LLNRK SF13X L15S
A70QS L70QS FWP L70QS LOSRK LLSRK_ID SF25X L25S
ABC 314 FWX L25S *
†
LPCC CCMR SF50P L50QS
ACK CCK GDA 216 LPJ (SP) JTD_ID SF60X L60S
AG SLC GDB 217 LPNRK (SP) LLNRK
§
SF70P L70QS
AGA AGA GDC 218 LPSRK (SP) LLSRK_ID SFE SFE
AGC 312 GDL 313 MCL KLK SL SLO
AGU (1-30A) BLN GEB LEB MCR 251 T TOO
AGW AGW GEBN LET MDA 326 TJN JLLN
AJT JTD_ID GFA 251 MDL 313 TJS JLLS
AMG MEG GFN FLA MDQ 313 TL TLO
AMI MID GGC 312 MDV 315 TR FLNR_ID
‡ / §
ANL CNL
§
GGM 235 MDX 313 TRM FLM
ANN CNN_E GLR LGR MEN FLM TRN-R FLNR_ID
‡ / §
ASO SPF GMA 235 MEQ FLQ TRS FLSR_ID
§
ATC ATO (287) GMD 239 MID FLA TRS-R FLSR_ID
§
ATC FLNR_ID
‡
GMT 481 MOF BLN XL25X L25S
ATDR CCMR
§
HCLR KLKR MOL BLF XL50F L50QS
ATM (Mersen) KLKD HCTR KLDR MTH 312 XL70F L70QS
ATMR KLKR
§
HEB LEB NCLR KLNR
ATQ FLQ HET LET NON NLN
ATQR KLDR HLR LHR
AX 481 HP10M SPF
A_UD PSR HP6J SPFJ *
BAF BLF HSJ LDFJ
BAN BLN JDL JTD_ID
BBS BLS JFL JLS
A fuse may be used in circuits where the fuse’s voltage rating is equal to or greater than the circuit
voltage, unless otherwise stated on the fuse. For example, the FLSR_ID indicating fuse has a voltage
rating of 75–600 volts. This fuse can be used on 600 volts, 480 volts, 250 volts, 125 volts, or 75 volts.
Never use a fuse in a circuit having a higher rated voltage than the fuse.
* Check specic mounting dimensions before substituting.
† Check characteristics and dimensions for application before substituting.
‡ For 1/10–30 amperes, order non-indicating FLNR series fuses.
§ Verify voltage for dc applications.
+ Littelfuse product is a non-renewable fuse.